IOM97-1163-01 Rev. DUltraWave Ultrasonic Liquid Level Installation & Operation Manual

Seite 2

IV. MECHANICAL INSTALLATIONGENERAL INSTALLATION GUIDELINES• Aim the transducer perpendicular to the surface of liquids.• Provide sufcient exible

Seite 3 - CONTENTS

This is required to avoid having material within the transducer’s blind space (amount of time required for transducer vibration to decay to a level wh

Seite 4 - CAUTION:

MOUNTING TEMPERATURE PROBELocation Guidelines:• Ensure that the temperature probe does not come in contact with the liquid during normal ll and duri

Seite 5 - I. HANDLING AND STORAGE

2. Drill the mounting holes.3. Attach the junction box using hardware that will secure it rmly in place.Note: Mounting hardware for the junction bo

Seite 6 - II. GENERAL SAFETY

1097-1163-01 Rev. Dwww.kistlermorse.com

Seite 7 - III. PRODUCT DESCRIPTION

1197-1163-01 Rev. Dwww.kistlermorse.com

Seite 8 - TRANSDUCER SPECIFICATIONS

1297-1163-01 Rev. Dwww.kistlermorse.com

Seite 9

1397-1163-01 Rev. Dwww.kistlermorse.com

Seite 10 - IV. MECHANICAL INSTALLATION

1497-1163-01 Rev. Dwww.kistlermorse.com

Seite 11 - 97-1163-01 Rev. D

1597-1163-01 Rev. Dwww.kistlermorse.com

Seite 13

1697-1163-01 Rev. Dwww.kistlermorse.com

Seite 14

ventureM E U R EA STNEM1797-1163-01 Rev. Dwww.kistlermorse.com

Seite 15

V. ELECTRICAL INSTALLATIONWARNING: VERY HIGH VOLTAGE IS PRESENT. REMOVE POWER FROM THE UNIT BEFORE INSTALLING, REMOVING, OR MAKING ADJUSTMENTSGENERAL

Seite 16

Notes:1. Seal all conduit ttings against water entry. Install drain holes at conduit’s lowest elevation(s) to allow condensation to drain.2. Wiring

Seite 17

2097-1163-01 Rev. Dwww.kistlermorse.com

Seite 18

Figure 4: Wiring Transducers to ControllerThe current output transmitter drives a maximum load of 600 ohms. If an external current loop power supply i

Seite 19

2297-1163-01 Rev. Dwww.kistlermorse.com

Seite 20

2397-1163-01 Rev. Dwww.kistlermorse.com

Seite 21

2497-1163-01 Rev. Dwww.kistlermorse.com

Seite 22 - V. ELECTRICAL INSTALLATION

2597-1163-01 Rev. Dwww.kistlermorse.com

Seite 23

I. HANDLING AND STORAGE ... 1II. G

Seite 24

2697-1163-01 Rev. Dwww.kistlermorse.com

Seite 25

2797-1163-01 Rev. Dwww.kistlermorse.com

Seite 26

2897-1163-01 Rev. Dwww.kistlermorse.com

Seite 27

2997-1163-01 Rev. Dwww.kistlermorse.com

Seite 28

3097-1163-01 Rev. Dwww.kistlermorse.com

Seite 29

VI. SET-UP SETTING SERIAL ADDRESSESThe controller will monitor up to 16 channels, with each channel having its own address. The SW2 switch, located o

Seite 30

INSTALLING PCBSThe UltraWave Series controller arrives from Kistler-Morse with the specied PCBs installed. However, you can expand your system. There

Seite 31

The controller keyboard is used to access the different menus, scroll through the vessel monitoring display screens, and enter setup and calibration p

Seite 32

time. To scroll through the menus, use the Up and Down Arrow Keys. Note: The controller must be in the Manual Mode (Auto LED off) to access the menus.

Seite 33

(BACKSPACE ARROW) KEYThe Backspace key is used to back up the cursor on the LCD display when using the alphanumeric keypad.“.” (PERIOD) KEYWhen the co

Seite 34

SAFETY SYMBOLSWARNING:IDENTIFIES CONDITIONS OR PROCEDURES, WHICH IF NOT FOLLOWED, COULD RESULT IN SERIOUS INJURY. RISK OF ELECTRICAL SHOCK.CAUTION:IDE

Seite 35 - VI. SET-UP

‘Enter’ to Copy> 25.0 ftPress the Up/Down Arrow Keys to switch to the previous channel (ID#01). When the display shows the desired channel, press t

Seite 36

The menu tree of the UltraWave Series controller is used to enter and view settings, set up, calibrate, and troubleshoot for the system. There are nin

Seite 37

Figure 10b: 30 Relay Set PointFigure 10c: 50 Serial / PLC3897-1163-01 Rev. Dwww.kistlermorse.com

Seite 38

Figure 10d: 70 Range FiltersFigure 10e: 90 Service Menu3997-1163-01 Rev. Dwww.kistlermorse.com

Seite 39

OPERATING THE ULTRAWAVE SERIES IN LEVEL APPLICATIONSINTRODUCTIONThe UltraWave Series is designed to get you up and running quickly once the system is

Seite 40 - Figure 9: Level Parameters

4. Press ENTER and the display shows:Transducer Freq* 43 KHz The model number of the transducer indicates the nominal frequency of operation: SC43PT

Seite 41

2. If Full Point is less than the Minimum Range for the transducer, be aware that the UltraWave Series will not detect or report material levels near

Seite 42 - Figure 10c: 50 Serial / PLC

INTRODUCTIONRefer below to the block diagram of the initial part of the Startup Procedure, and Figure 15 for the remainder of the Startup Procedure. T

Seite 43 - Figure 10e: 90 Service Menu

Figure 15: Flow Start-Up Procedure* Kennison:The 20” Kennison Nozzle is the only nozzle size currently available. If you select another Kennison nozzl

Seite 44 - Figures 12 and 13

START-UPWhen performing the Startup Procedure, do not worry if you make an error. The parameters can be corrected after you complete the startup, in t

Seite 45

I. HANDLING AND STORAGESAVE THESE INSTRUCTIONSINSPECTIONS AND HANDLINGDo not dispose of the carton or packing materials.Each package should be inspec

Seite 46 - Example 2:

Press the arrow keys to access the options of the Weir Menu. Press Enter for your desired options. Once completed, you will go to Step 9, Select Flo

Seite 47 - See Figure 16):

14. For Auto and Manual calibration, the display shows:Maximum Head Hgt> .0 in Use the keypad or the up/down arrow keys to enter the Maximum Head

Seite 48 - * Kennison:

Figure 17: Flow Calibration MenuPrim: Select primary element type and sizeZero: Calibrate the systemSim: Simulate head to check corresponding owUnit:

Seite 49

• Curr Head — The current head; to perform an accurate calibration, measure this just before you input the value.• Zero Dist — The distance from the

Seite 50

26 RESETThe ReSet Menu allows you to reset calculated ow values:• Minimum ow (MinF) — reset to the current ow rate• Maximum ow (MaxF) — reset to

Seite 51

ULTRAWAVE SERIES MENU DESCRIPTIONSMENU OPTIONSThe following options are available from the MENU key in manual mode: • 10 Display: Select desired disp

Seite 52

11 STD FORMATSelect a format from the menu options:XXXX.XXXX.XXXXXXX12 STD UNITSSelect the desired units: Feet, Inches, Meters, or Centimeters13 SPEC

Seite 53

displayed is 120% while the graph remains at 100%.The default for the display is bar graph Off (bar graph not displayed when vessel monitoring). The c

Seite 54

21 FULL POINTRefer to Figure 12. Full Point is the distance from the face of the transducer to the top of the Span. Modifying Full Point allows you to

Seite 55

25 TEMPERATUREThis menu sets up the temperature compensation parameters. Temperature has three submenus: Fixed, Monitor, and Scale.FIXED (FIXED TEMPER

Seite 56

II. GENERAL SAFETYAUTHORIZED PERSONNELAll instructions described in the document must be performed by authorized and qualied service personnel only.

Seite 57

• Enable — turns linearization on and off.• Number of points — allows you to select the number of points to input for the linearization (32 maximum

Seite 58

The Relay Set Pt section denes each of the parameters.31 REPORTWhen this menu is accessed, the display shows all setpoints assigned to the current ch

Seite 59

be programmed to pulse a remote totalizer or telemetry system. OnTm (ow applications only) - if you want the relay to pulse once it is activated, thi

Seite 60

the setpoints by pressing the Up and Down Arrow Keys until the setpoint you want to delete is displayed. Then, press the Enter Key.Caution: Manually a

Seite 61

Current output is typically used to retransmit continuous level/ow data to a remote display or PLC/Distributed Control System (DCS). The current outp

Seite 62

Note: The value entered for the 4/0 mA operation point does not have to be smaller than the value entered for the 20 mA operation point.Note: See Figu

Seite 63

Pressing the ESC Key or Scan/Hold Key terminates the function. Once the test is terminated, the current outputs return to automatic control.Caution: M

Seite 64

49 MODE The current transmitter can be set up to output 0-20 mA or 4-20 mA. This menu is used to select one of the two operating modes. The controller

Seite 65

Figure 24: Transducer Menu Tree61 FREQUENCYFrequency has three submenus:• Target — under Target, the target frequency of the transducer set up for th

Seite 66

the vessel full point. TVG affects the sensitivity of the system in detecting return echoes by amplifying the return signal in relation to the time it

Seite 67

III. PRODUCT DESCRIPTIONThe UltraWave Series Ultrasonic System can monitor up to a total of 8 transducers of various frequencies, accommodating multi

Seite 68

67 MID GAIN ADJ (CONSULT KISTLER-MORSE BEFORE MODIFYING!)Mid Gain Adj allows the adjustment of the TVG curve in the middle distance ranges. It is gene

Seite 69

minimum range should be extended past the obstructions to eliminate the possibility of interference. Minimum Range has a submenu; Manual.MANUALMin Ran

Seite 70

example 1, if a large signal change is detected that falls outside of the window, the UltraWave Series immediately moves the location of the reference

Seite 71

update the level measurement. The default for Std Dev Ratio is 3.0.• Listen Deviation monitors the listen deviation value. The absolute value of each

Seite 72

based on the transducer’s maximum range, before it transmits the next signal, regardless of how quickly the previous signal was returned. MaxRange is

Seite 73

UltraWave Series10 Display3. Scroll with the arrow keys to the 90 Service Menu option. Press Enter. The display shows: Service Menu91 Access4. Press

Seite 74 - 90 SERVICE MENU

92 DEFAULTThis function clears all UltraWave Series setup parameters, resets them to factory default values, and automatically leads you through the S

Seite 75

Manual Mode. The Auto LED turns off.2. Press the Menu Key to display the Main Menu. 3. Press the up/down arrow key until 90 Service Menu appears. Pr

Seite 76

Cx=(‘C’ ‘+’ ‘*’ "9. Press the F1 Key to select C. Press 1 on the keypad. Press the F2 Key to select +. The display shows:Cx=(C1+‘C’ ‘+’ ‘*’ &quo

Seite 77

Channel x will now display the average of the vessels in vessel 1 through 4.C Identies a specic channel in the equation. C must be immediately fo

Seite 78

CONTROLLER SPECIFICATIONSFUNCTIONALOperating Power 110/230 VAC (+/- 10%) 50/60 Hz or 24 VDCPower Requirement 20 VACOperating Temperature -5º to 122º F

Seite 79

Correct (no spaces): C9=C3+C4+C6• The controller interprets equations using standard math rules regarding order of operations. If you are unsure

Seite 80

DEFAULT NVRAM (RESET RAM MEMORY)This function resets the non-volatile RAM (NVRAM) on the Microprocessor PCB. This resets all parameters to the factory

Seite 81

COMMAND FUNCTION MASTER TO ULTRAWAVE SERIES TRANSMITTED BY MASTER FROM ULTRAWAVE SERIESRECEIVED BY ULTRAWAVE SERIESHEX ASCII23 # Kistler-Morse product

Seite 82 - CHARACTER DEFINITION

CHECKSUM CALCULATIONThe one-byte checksum is calculated by adding the Hex values of all ASCII characters between the start of message character ‘>’

Seite 83 - Example:

ExamplesFor each command below, the general format of the command is shown above the example.‘#’ COMMAND — KISTLER-MORSE PRODUCT IDENTIFICATION NUMBER

Seite 84

‘T’ COMMAND — REQUEST TOTALIZER DATA (FLOW APPLICATIONS ONLY)This command is sent by the master to request the controller to send the totalizer data.

Seite 85 - VII. MAINTENANCE

VIII. TROUBLESHOOTINGProblem SolutionYou applied power to the unit, but the display does not come on.1. Check fuse F1. If blown, replace.2. If the

Seite 86 - VIII. TROUBLESHOOTING

Problem SolutionThe controller is displaying data while channel monitoring, but the value does not agree with the known measured level in the vessel.1

Seite 87 - Problem Solution

ERROR MESSAGESFor each error message, one or more possible explanations and suggested solutions are provided. Note: Write down all existing system par

Seite 88

4. UNITS OVERRANGEExplanation: The calculated level exceeds the maximum number for a 16-bit system (65535).Solution a. If you selected special display

Seite 89

Figure 1. UltraWave Series Ultrasonic System Con guration Diagram597-1163-01 Rev. Dwww.kistlermorse.com

Seite 90

ERROR CODESIf you make an error entering an equation in a math channel, the controller will respond in one of two ways:• After you enter the equation

Seite 91

2. Equation tries to take a square root of a negative number that is calculated as part of the equation (i.e., square root of (8-12).3. Equation tri

Seite 92

Mode you can change the display to show any of the following parameters: Head (current head), Temperature (current temperature), Total (total ow sinc

Seite 93

8997-1163-01 Rev. Dwww.kistlermorse.com

Seite 94

9097-1163-01 Rev. Dwww.kistlermorse.com

Seite 95

9197-1163-01 Rev. Dwww.kistlermorse.com

Seite 96

2014 All rights reserved.All data subject to change without notice.97-1163-01 Rev. D150 Venture Boulevard Spartanburg, SC 29306Tel: (800) 426-9010Te